PS16 – PS17 POWER SUPPLYS

PS16 – PS17 POWER SUPPLYS

0

For proper operation, the unit should be tested at least once a year as described below:
Output voltage test:
Check DC output for proper voltage level under normal load conditions.
Battery test:
Check specified voltage, at both battery terminal and board terminals marked [+VBAT and 12VDC (-)] under normal load conditions, verify that the battery is fully charged and insure there is no break in the battery connection wires.

Compare
Category: Tags: , , , , , , , , , ,
   

Share this product

The power supply’s above convert 230/120VAC 50/60Hz input, to a 12 VDC power limited output (see specification) with an integrated battery charger. Designed for use with all stand-alone access control units (ACU).

Overview

The power supply should be installed in accordance with article 760 of the National Electric Code NFPA 72 as well as applicable Local Codes.
Note: Circuit breaker must be close to the power supply and must be accessible.
1. Mount the Power Supply
2. Connect AC power (120VAC/60Hz or 230VAC/50Hz to the marked terminals, “Phase” to [L] and “Neutral” to [N]. Use 18 AWG or larger for all power connections (Battery, DC output).
3. Connect the grounding to the ground terminal.
Make sure to secure the screw tightly.
4. Connect the ACU power input to the power terminal marked [VOUT + and 12VDC(-)] 5. Backup Battery is optional. When battery is not used, loss of AC will result in the loss of output voltage. When using a backup battery, it must be a UL certified “lead acid” or “gel” type. Connect the battery terminal to power terminal marked [+VBAT and 12VDC (-)] (Battery leads included)

Specifications

ELECTRICAL SPECIFICATIONS
Input:
PS-C16 230/16VAC ~ 50Hz (25VA) Class 2 rated
250V/1.0A Time Lag (slow blow) fuse protection.
PS-C16U 120/16VAC ~ 60Hz (25VA) Class 2 rated
250V/1.5A Time Lag (slow blow) fuse protection.
PS-C17 230/16VAC ~ 50Hz (40VA) Class 2 rated
250V/1.0A Time Lag (slow blow) fuse protection.
PS-C17U 120/16VAC ~ 60Hz (40VA) Class 2 rated
250V/1.5A Time Lag (slow blow) fuse protection.
ACU Output:
PS-C16/U 12 VDC, 1.2A continuous supply. (current limit)
PS-C17/U 12 VDC, 2.0A continuous supply. (current limit)
Battery Backup
Built in charger for sealed UL certified battery lead acid or gel up to 7AH
Maximum charge current 1.2A
Automatic switch over to stand-by battery when AC fails
Caution: Risk of explosion, when battery is replaced by a wrong battery type.
Visual indicator
DC output LED indicator on PCB
AC input LED indicator, board terminal marked [POWER LED & (-) ] Additional Features
Short circuit and thermal overload protection
Includes battery leads
ENVIRONMENTAL SPECIFICATIONS
Operating Temperature:
14°F to 158°F (-10°C to 70°C)
Operating Humidity:
0 to95% (Non-Condensing)
MECHANICAL SPECIFICATIONS
Dimensions:
Height: 8.85″ (225mm) Width: 9.05″ (230mm) Depth: 0.30″ (76mm)